Notes:
THESE ARE GENERAL NOTES; ITEMS CAN BE VERIFIED IN THE FIELD.
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
002. ONLY ALUMINIM WIRE PERMITTED IS SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
003. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
004. DELETE
005. DELETE
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2005 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE ALONG WITH THE FOLLOWING COMMENTS.
008. DELETE
009. DELETE
010. ALL EXTERIOR LIGHTING SHALL COMPLY WITH COMPREHENSIVE ZONING ORDINANCE ARTICLE IV SECTION 6 LIGHTING & GLARE RQ'MENTS.
110. AN AS-BUILT LEGIBLE PANEL SCHEDULE SHALL BE AFFIXED TO THE INSIDE OF ELECTRICAL PANELS FOR EACH TENANT.
220. DELETE
277. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250.
480. DELETE
INSTALL ELECTRICAL SERVICE TO PATIO COVER