Notes:
THESE ARE GENERAL NOTES; ITEMS CAN BE VERIFIED IN THE FIELD.
001. MINIMUM #12 COPPER CONDUCTORS PERMITTED----------------------- EXCEPT FOR CONTROLS.
006. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
007. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2005 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE ALONG WITH THE FOLLOWING COMMENTS.
008. ANY WIRE/CONDUCTORS USED IN HVAC PLENUM AREA SHALL BE PLENUM RATED.
009. DELETE
011. AN AS-BUILT LEGIBLE PANEL SCHEDULE SHALL BE AFFIXED TO THE INSIDE OF ELECTRICAL PANELS FOR EACH TENANT.
PROVIDE 1 HR. RATED ELECTRICAL OUTLET BOXES IN @ I HR. CORRIDOR AND @ DEMISING WALLS.
INSTALL MAG-LOCK ACCESS CONTROLLERS