Notes:
8/23/2018 12:17:53 PM
MOVING GFCI, LIGHT SWITCH AND OUTLET.
STANDARD ELECTRICAL COMMENTS:
300. ALL WORK PERFORMED MUST MEET THE 2014 NEC AND 2015 IRC & IBC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
301. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS
302. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS
303. LIGHTING COM-CHECKS MUST MATCH PLANS
304. NO ALUMINIM WIRE PERMITTED OR #14. SERVICE AND FEEDER CONDUCTORS PERMITTED 1/0 AND LARGER
305. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
306. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2015 IBC.
307. LIGHTING AND CONTROLS SHALL COMPLY WITH 2015 IECC WHERE APPLICABLE.
309. ALL TERMINATIONS SHALL BE TIGHTENED TO MANUFACTURERS TORQUE SPECIFICATIONS
310. SIZE GROUNDING ELECTRODE CONDUCTOR FROM TRANSFORMER PER TABLE 250.66, 2014 NEC
311. SEE ARTICLE 700.7 G, 2014 NEC FOR SIGN AT SERVICE EQUIPMENT
312. AVAILABLE FAULT CURRENT SHALL BE LABELED ON SERVICE EQUIPMENT 110.24, 2014 NEC
314. LABEL VOLTAGE AND COLOR OF EACH PHASE CONDUCTOR AND NEUTRAL CONDUCTOR ON FRONT PANEL COVERS
315. PHASE TAPE NOT PERMITTED ON NEUTRAL AND GROUNDING CONDUCTORS NUMBER 6 AND SMALLER
316. IDENTIFY ALL CONDUCTORS WITH THE CORRECT COLOR AT EVERY JUNCTION POINT