STANDARD EQUIPMENT:
300. ALL WORK PERFORMED MUST MEET THE 2014 NEC AND 2015 IBC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
301. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS
302. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS
304. NO ALUMINIM WIRE PERMITTED OR #14. SERVICE AND FEEDER CONDUCTORS PERMITTED 1/0 AND LARGER
305. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
309. ALL TERMINATIONS SHALL BE TIGHTENED TO MANUFACTURERS TORQUE SPECIFICATIONS
310. SIZE GROUNDING ELECTRODE CONDUCTOR FROM TRANSFORMER PER TABLE 250.66, 2014 NEC
311. SEE ARTICLE 700.7 G, 2014 NEC FOR SIGN AT SERVICE EQUIPMENT
312. AVAILABLE FAULT CURRENT SHALL BE LABELED ON SERVICE EQUIPMENT 110.24, 2014 NEC