300. ALL WORK PERFORMED MUST MEET THE 2014 NEC AND 2015 IRC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
301. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS
302. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS
304. NO ALUMINIM WIRE PERMITTED OR #14. SERVICE AND FEEDER CONDUCTORS PERMITTED 1/0 AND LARGER
309. ALL TERMINATIONS SHALL BE TIGHTENED TO MANUFACTURERS TORQUE SPECIFICATIONS
310. SIZE GROUNDING ELECTRODE CONDUCTOR FROM TRANSFORMER PER TABLE 250.66, 2014 NEC
312. AVAILABLE FAULT CURRENT SHALL BE LABELED ON SERVICE EQUIPMENT 110.24, 2014 NEC
317. SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTION.
8/12/2019 3:28:01 PM
8/13/2019 2:16:54 PM
70 AMP 120/240 VOLT STAND ALONE SERVICE