Notes:
9/3/2019 1:18:30 PM
DEMETRI BOULIGNY
ELECTRICAL REVIEW
300. ALL WORK PERFORMED MUST MEET THE 2014 NEC AND 2015 IRC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.
305. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
306. PROVIDE EXIT AND EMERGENCY LIGHTING AS NOTED AND REQUIRED PER 2015 IBC.
308. ALL EXTERIOR LIGHTING SHALL COMPLY WITH CITY OF FRISCO ZONING ORDINANCE 4.05
317. SUBJECT TO FIELD INSPECTION APPROVAL. CALL (972) 292-5386 FOR INSPECTION.
315. PHASE TAPE NOT PERMITTED ON NEUTRAL AND GROUNDING CONDUCTORS NUMBER 6 AND SMALLER
316. IDENTIFY ALL CONDUCTORS WITH THE CORRECT COLOR AT EVERY JUNCTION POINT
314. LABEL VOLTAGE AND COLOR OF EACH PHASE CONDUCTOR AND NEUTRAL CONDUCTOR ON FRONT PANEL COVERS
313. BATTERY BACKUP EMERGENCY LIGHT REQUIRED AT GENERATOR
312. AVAILABLE FAULT CURRENT SHALL BE LABELED ON SERVICE EQUIPMENT 110.24, 2014 NEC
310. SIZE GROUNDING ELECTRODE CONDUCTOR FROM TRANSFORMER PER TABLE 250.66, 2014 NEC
311. SEE ARTICLE 700.7 G, 2014 NEC FOR SIGN AT SERVICE EQUIPMENT
309. ALL TERMINATIONS SHALL BE TIGHTENED TO MANUFACTURERS TORQUE SPECIFICATIONS
307. LIGHTING AND CONTROLS SHALL COMPLY WITH 2015 IECC WHERE APPLICABLE.
9/3/2019 1:17:59 PM