Permit Info
Short Description:
WATER TOWER CELL EQUIPMENT
Approved Date:
11/18/2019
Notes:
11/18/2019 12:38:03 PM
Electrical 16-12-101
1- All work performed must meet the 2014 NEC and abide by the city of Frisco Zoning ordinance (13-06-36), and all other city ordinances.
2-Minimum #12 copper conductors permitted except for controls.
4-Lighting COMchecks must match plans.
5-No Aluminum wire permitted or #14. service and feeder conductors permitted 1/0 and larger.
6-Pull equipment grounds in all raceways.
7-Provide exit and emergency lighting as noted and required per 2015 IBC.
8-lighting and controls shall comply with the 2015 IECC where applicable.
9-Available fault current shall be labeled on service equipment 110.24, 2014 NEC.
10-Subject to field review and inspection- call (972) 292-5386 for inspection or schedule online at https://etrakit.friscotexas.gov/
Parcel Info
City/State/Zip:
FRISCO, TX, 75034
Subdivision:
WARREN PARKWAY R-O-W AND FIRE STATION NO 3 (CFR)
|
OWNER | FRISCO CITY OF | ()- | | | FRISCO, TX 75034-3253 |
APPLICANT | AT & T | (281)405-6747 | | | FARMERS BRANCH, TX 75234 |
CONTRACTOR | TBD | ()- | | | |
ARCHITECT | CLS GROUP | (405)348-5460 | | | RALEIGH, NC 27603 |
Total Fees |
Charged: $45.00
Balance Due: $45.00
|
There are currently no inspections on this record.
|
ELECTRICAL REVIEW | CRYSTAL FAUSS | APPROVED AS NOTED | 11/12/2019 | 11/18/2019 | |
More Info
|
INITIAL REVIEW | TREB DUMA | ACCEPTED | 11/12/2019 | 11/14/2019 | 11/26/2019 |
More Info
|