2017 NEC Commercial Electrical Plan Review Notes
1- All work performed must meet the 2017 NEC and abide by the City of Frisco Zoning ordinance, and all other City ordinances.
2- Minimum #12 copper conductors permitted except for controls.
3- Lighting COMchecks must match plans.
4- Aluminum conductors permitted for service and feeder conductors 1/0 and larger.
5- Pull equipment grounds in all raceways.
6- Provide exit and emergency lighting as noted and required per 2018 IBC.
7- lighting and controls shall comply with the 2018 IECC where applicable.