Notes:
ADD 5 NEW LIEBERT UNITS TO IDF ROOM
5/10/2013 12:00:00 AM
1. ALL DUCT WORK TO BE SEALED WITH MASTIC, WELDS, OR GASKETS; TAPES NOT ACCEPTED.
2. ALL EXHAUST FANS TO TERMINATE OUTSIDE OF THE BLDG.
3. FRESH AIR INTAKES TO BE 10 FT. AWAY OR 2 FT. BELOW EXHAUST GAS OPENINGS & REQUIRE DAMPERS TO CLOSE INTAKE WHEN NOT IN USE.
4. MECH. CONTRACTOR TO BE RESPONSIBLE FOR DUCT SIZING AND LOAD CALCULATION.
5. MECH. CONTRACTOR TO VERIFY FRESH AIR INTAKE PER IMC 403 & TABLE 403.3
6. MECH. INSTALLATION TO COMPLY WITH 2009 IECC AND SUPPLEMENTS.
7. RIGID DUCT REQUIRED WITH 6 FT. (R-6) FLEX DUCT CONNECTOR ALLOWED BETWEEN RIGID DUCT AND DIFFUSER.
8. SET BACK T-STATS REQUIRED FOR EACH ZONE.
9. SMOKE DETECTORS/DAMPERS TO BE INSTALLED PER CHAPTER 6 OF IMC.
10. SUBJECT TO FIELD REVIEW AND INSPECTION.