Notes:
POOL & SPA / HOMEWOOD SUITES HOTEL
9/26/2007 12:00:00 AM
COMMENTS FROM HEALTH & FOOD SAFETY:
HOMEWOOD SUITES POOL/SPA AND BARRIER:
- POOL BARRIER INCLUDING ALL ENTRIES/EXITS MUST MEET STATE MINIMUM STANDARDS. SPACING IN FENCE NOT EXCEED 4 INCHES. GATES TO SELF CLOSING/LATCHING AND BE LOCKABLE. NO CLIMB HAZARDS WITHIN 3 FT. OF BARRIER.
- RESTROOM LAVATORIES MUST HAVE TEMPERED HOT WATER (90 - 110 DEGREES) AND DRAIN TO SANITARY SEWER.
- PROVIDE AND LOCATE WATER DRINKING FOUNTAINS.
- EQUIPMENT ROOM MUST HAVE ADEQUATE VENTILATION - LOUVERED OR MECHANICAL - AND HAVE LOCKABLE ACCESS.
- ALL LEADING EDGES OF BENCHES, STEPS AND LEDGES REQUIRE 1 INCH MINIMUM TILE STRIPE.
- LIGHTS MUST BE PROTECTED BY GFCI. EQUIPMENT ELECTRICAL DISCONNECT MUST BE VISIBLE INSIDE POOL EQUIPMENT ROOM.
- PROVIDE AND LOCATE CHAIRLIFT SLEEVE (MUST BE IN SHALLOW END OF POOL AND WITHIN 24 INCHES OF WATER'S EDGE). SLEEVE MUST BE BONDED.
- TWO SETS OF SAFETY EQUIPMENT ARE REQUIRED ON POOLS OVER 2000 SQ FT OF SURFACE AREA.
- AUTOFILL LINE, IF PROVIDED, MUST NOT PROTRUDE BEYOND COPING EDGE.
- PROVIDE AND LOCATE KNOX BOX LOCATED OUTSIDE OF POOL BARRIER. - PROVIDE AND LOCATE EMERGENCY 911 PHONE OUTSIDE OF POOL BARRIER IF LOCKED.
- DEPTH, NO DIVING, AND INTERNATIONAL SYMBOL MARKERS MUST BE PROVIDED MINIMUM OF EVERY 25 FT.
- ENTRY/EXITS MUST BE PROVIDED EVERY 75 FT. OF POOL WALL LENGTH OR FRACTION OF AND BE INSTALLED ACCORDING TO STATE MINIMUM STANDARDS.
- SPA SHUT OFF SWITCH AND SIGNAGE REQUIRED AND MUST MEET CODE.
- SKIMMER EQUALIZER LINES ARE NOT ALLOWED.
- POST CONTRUCTION ENGINEERS LETTER TO BE ONSITE AT POOL FINAL.
- APPROVED PERMIT SET OF PLANS TO BE ON JOBSITE AT ALL TIMES.
- ALL SIGNAGE REQUIRED BY STATE CODE AND POOL ORDINANCE MUST BE INSTALLED AT POOL FINAL.
- HANDHOLDS AND COPING SHALL BE PROVIDED AROUND THE POOL PERIMETER IN AREAS WHERE DEPTHS EXCEED 42". HANDHOLDS < 2' APART AND MEET MINIMUM STANDARDS FOR SIZE AND INSTALLATION.