Notes:
100 SQ FT / FOUNTAIN / WATER FEATURE
3/15/2011 12:00:00 AM
COMMENTS FROM HEALTH & FOOD SAFETY:
STONEWATER CROSSING – FOUNTAIN:
- BUILDING INSPECTIONS APPLY TO FOUNTAINS.
- LIGHTS MUST BE PROTECTED BY GFCI. EQUIPMENT ELECTRICAL DISCONNECT MUST BE VISIBLE INSIDE EQUIPMENT ROOM.
- APPROVED PERMIT SET OF PLANS TO BE ON JOBSITE AT ALL TIMES.
- A MINIMUM OF FOUR (4) SIGNS MUST BE PLACED AROUND COPING OR FOUNTAIN WALL, STATING “FOUNTAIN – NO SWIMMING – NO DIVING”.
- MAIN DRAIN COVERS OR GRATES MUST BE VGB COMPLIANT AND ASME/ANSI A112.19.8 – 2007 OR SUCCESSOR STANDARD APPROVED, BE HYDRAULICALLY BALANCED, AND MUST HAVE MINIMUM 3’ SEPARATION, INSIDE EDGES OF COVER/GRATE TO COVER/GRATE.
- SUCTION SYSTEMS TO BE PLUMBED ACCORDING TO ENGINEERED PLANS AND DRAWINGS.
- SUCTION SYSTEMS MAY NOT EXCEED APPROVED FLOW RATES (APPROVED GPM OR 1.5 FPS) OF COVERS/GRATES WHEN PUMPS RUNNING AND WITH ONE COVER/GRATE 100% BLOCKED.
- FOUNTAIN DEPTH CANNOT EXCEED 18”.
- CIRCULATION SYSTEMS CONSISTING OF PUMPS, PIPE, FILTERS, AND AUTOMATED CHLORINATORS SHALL BE PROVIDED AND DESIGNED TO MAINTAIN A HEALTHY FOUNTAIN ENVIRONMENT. MUST MAINTAIN STATE MINIMUM STANDARDS FOR WATER QUALITY.
-IF CONSTRUCTION IS COMPLETE, AN ENGINEER’S LETTER IS REQUIRED.