Notes:
EMERSON FOUNTAIN
7/23/2013 12:00:00 AM
1. MINIMUM DUAL MAIN DRAINS REQUIRED FOR EACH SUCTION PUMP. APPROVED DRAIN COVERS OR GRATES (ASME/ANSI A112.19.8M) NOT HAVING WATER FLOW THAT EXCEEDS 1.5 FPS THROUGH REMAINING DRAIN/GRATE WITH ONE DRAIN/GRATE 100% BLOCKED. COVERS OR GRATES MUST HAVE MINIMUM OF 3' SEPARATION, INSIDE EDGES OF COVER TO COVER OR GRATE TO GRATE.
2. MINIMUM OF FOUR (4) TILE SIGNS PLACED AROUND COPING OF FOUNTAIN, STATING "FOUNTAIN, NO SWIMMING, NO DIVING".
3. FOUNTAIN DEPTH CANNOT EXCEED 18".
4. CIRCULATION EQUIPMENT SHALL BE PROVIDED AND DESIGNED TO MAINTAIN A HEALTHY FOUNTAIN ENVIRONMENT. PROVIDE OBSERVABLE WASTE WATER DISCHARGE, SITE GLASS, OR FREE FALL.
5. FOUNTAIN MUST MEET REQUIREMENTS OF ALL BUILIDING CODES AS AMENDED AND ADOPTED.
6. MAKE-UP WATER REQUIRES RPZ.
7. PROVIDE A PUMP SUCTION, FILTER INLET & OUTLET GAUGE & INSTALL A FLOW METER ON EQUIPMENT. LABEL ALL PIPING TO INDICATE SOURCE AND DIRECTION OF FLOW.
8. MOTORS SHALL COMPLY WITH UL REQUIREMENTS.
9. PUMP MOTORS MUST BE INTERNALLY AND EXTERNALLY GROUNDED.
10. ELECTRICAL EQUIPMENT MUST BE INSTALLED PER CURRENT NEC.
11. ALL EXTRA STRUCTURES NOT PART OF THE FOUNTAIN REQUIRES A SEPARATE PERMIT.