Notes:
FOUNTAIN
7/18/2014 12:00:00 AM
(7/18/2014 3:23 PM SML)
- BUILDING INSPECTIONS APPLY TO FOUNTAINS.
- APPROVED PERMIT SET OF PLANS TO BE ON JOBSITE AT ALL TIMES.
- DUAL HYDRAULICALLY BALANCED MAIN DRAINS REQUIRED ON EACH SUCTION SYSTEM INCLUDING CIRCULATION, BOOSTERS, WATER FALL OR FEATURES.
- MAIN DRAIN COVERS/GRATES MUST BE ANSI/ASME A112.19.8 - 2007 OR SUCCESSOR STANDARD APPROVED AND MUST HAVE MINIMUM 3 FT SEPARATION BETWEEN INSIDE EDGES OF COVER/GRATE TO COVER/GRATE UNLESS INACCESSIBLE. COVERS MUST NOT HAVE WATER FLOW THAT EXCEEDS THE APPROVED MAXIMUM GALLONS PER MINUTE AS LISTED ON THE COVER.
- ENSURE NO ENTRAPMENT HAZARDS.
- IF FOUNTAIN IS NOT USING FRESHWATER, CIRCULATION EQUIPMENT SHALL BE PROVIDED AND DESIGNED TO MAINTAIN A HEALTHY FOUNTAIN ENVIRONMENT.
- FOUNTAIN DEPTH CANNOT EXCEED 18” IN DEPTH.
- MAKE UP WATER REQUIRES RPZ.
- LIGHTS MUST BE PROTECTED BY GFCI. EQUIPMENT ELECTRICAL DISCONNECT MUST BE VISIBLE INSIDE EQUIPMENT ROOM.