Notes:
11/1/2019 8:35:42 AM
POST-CONSTRUCTION ENGINEER LETTER REQUIRED PRIOR TO POOL FINAL INSPECTION.
PROJECT MUST COMPLY WITH POOL ORDINANCE, TDSHS MINIMUM STANDARDS FOR POOLS AND SPAS, PIWF LAW AND ADA RULES. THIS INCLUDES SITE DECK AND POOL LIGHTING, RESTROOMS, ON-DECK SHOWER, EMERGENCY PHONE, POOL ENCLOSURE AND LIFEGUARD REGULATIONS. COORDINATION WITH POOL CONTRACTOR IS IMPERATIVE.
PRE-PLASTER INSPECTION DURING POOL CONSTRUCTION CANNOT BE APPROVED UNTIL PERMANENT ENCLOSURE IS INSTALLED AND APPROVED.
SALES OFFICE, RESIDENCES AND RECREATION BUILDING DOOR MUST NOT OPEN DIRECTLY INTO A POOL YARD.
A WALL OF A BUILDING MAY NOT BE USED AS PART OF A POOL YARD ENCLOSURE UNLESS EACH WINDOW IS PERMANENTLY CLOSED AND UNABLE TO BE OPENED.
3686 SQ. FT; 8 SKIMMERS; 13 RETURNS; 6 FLOOR INLETS MINIMUM.
FOUNTAINS AND WATER FEATURES MUST BE PERMITTED SEPARATELY. ALSO, ANY OTHER STRUCTURES IN POOL ENCLOSURE MUST BE SUBMITTED SEPARATELY.
911 PHONE MUST BE LOCATED OUTSIDE OF FENCE ENCLOSURE, WITHIN 100 FT OF POOL.
JOINTS AT COPING AND CONCRETE DECKS SHALL BE WATERTIGHT. DECK EDGES MUST BE ROUNDED, TAPERED OR SHAPED TO ELIMINATE SHARP CORNERS. DECK DRAINS SHALL NOT MIX WITH POOL WATER. SITE MUST BE GRADED TO DRAIN AWAY FROM POOL.
ALL SUCTION SUMPS MUST BE INSTALLED PRIOR TO B-STEEL INSPECTION.
ALL AUTO FILL LINES MUST HAVE RPZ.
SVRS REQUIRED FOR COVERS OR GRATES LESS THAN 24-INCH DIAGONAL IN WATER 4 FT DEEP OR LESS.
ANTI-VORTEX DRAIN COVERS WITH APPROVED STAMP ARE REQUIRED. THERE SHALL BE NO ENTRAPMENT HAZARDS. SUCTION OUTLETS SHALL BE MINIMUM OF 3FT. APART MAXIMUM 20 FT. AND PLACED AT THE LOWEST POINT OF THE POOL.
ALL FILTRATION SYSTEM MUST BACKWASH TO SANITARY SEWER SYSTEM INCLUDING RECIRCULATION SYSTEM. ALL FILTRATION SHALL HAVE MEANS TO OBSERVE WASTE DISCHARGE EITHER BY FREE FALL OR SIGHT GLASS.
REFER TO GAUGE DIAGRAM PROVIDED W1.11b; MISSING FILTER INLET GAUGE.
MUST LABEL CIRCULATION PIPING WITH FUNCTION AND FLOW DIRECTION.
COPING, HANDHOLDS, ROCKS, STONES, OR OTHER MATERIALS THAT ARE PART OF WATER OR OTHER FEATURES MAY NOT PROTRUDE MORE THAN 2" PAST THE POOL BEAM.
ENSURE JOINTS IN DECKING DO NOT EXCEED 0.25 INCH VERTICALLY AND 3/16 INCH HORIZONTALLY.
MUST NOT HAVE ANY CLIMB HAZARDS WITHIN 36 INCHES OF POOL ENCLOSURE; THIS INCLUDES GRILLS, LIGHTING, HAND RAILS ETC…
HANDRAILS MUST TERMINATE WITHIN 8” OF LAST STEP OR TO WATER DEPTH OF 36” FROMSTEP SURFACE.
MUST COMPLY WITH STATE STANDARDS FOR LADDERS.
MUST PROVIDE ELECTRICAL DISCONNECT FOR SERVICE PERSONNEL LOCATED WITHIN SIGHT OF EQUIPMENT. (BREAKERS WILL NOT SUFFICE RULE)
“NO DIVING” & INTERNATIONAL SYMBOL MUST BE 4 INCH LETTERING AND BE SPACED AT A MAX 25 FT INTERVALS.
MUST PROVIDE SIGNAGE IN COPING STATING ‘NO SWIMMING, NO DIVING” AT SCUPPERS.
REFER TO REDLINE ON W1.10. LOCATION FOR BOTH POOL LIFT SLEEVES ARE DENIED; RELOCATE POOL LIFT SLEEVE AWAY FROM STEPS AND WATER LOUNGES.
ALL SIGNAGE MUST COMPLY WITH SECTION 256.199 & CITY ORDINANCE; ALL SIGNAGE REQUIREMENTS CAN BE FOUND ON THE PLAN SUBMITTAL DOCUMENTS OR COMMERCIAL POOL AND SPA, PLAN DESIGN, REVIEW AND CONSTRUCTION CHECKLIST.
MUST PROVIDE A MINUMUM OF TWO SETS OF SAFETY EQUIPMENT.
ENCLOSURE MUST COMPLY WITH HEALTH & SAFETY CODE CHAPTER 757.
THERE SHALL NOT BE ANY OPENING > ½” IN ANY DIRECTION WITHIN 18” FROM THE LATCH, INCLUDING THE SPACE BETWEEN THE GATE AND THE GATE POST TO WHICH THE GATE LATCHES.
NO DOORS OF CLUBHOUSE, SALES OFFICE OR OTHER BUILDING SHALL OPEN DIRECTLY INTO THE POOL YARD UNLESS FOR ENTRY INTO STORAGE ROOM, RESTROOM, SHOWER, DRESSING OR MECHANICAL ROOM AND THE ROOM DOES NOT HAVE ANY DOOR OR GATE OPENINGS TO THE OUTSIDE OF THE POOL YARD OR ENCLOSURE.
HOT AND COLD WATER ARE REQUIRED AT PUBLIC LAVATORIES AND SHOWER; WATER SUPPLIED MUST BE TEMPERED VIA THERMOSTATIC MIXING VALVE TO MAXIMUM 110 DEGREES.
RESTROOMS AND RELATED FACILITIES SERVING POOL AREA MUST COMPLY WITH POOL ORDINANCE. RESTROOMS SHALL HAVE BABY CHANGING TABLES. WOMEN’S SHALL HAVE COVERED TRASH CAN OR FEMININE WASTE RECEPTACLE WITH COVER.
LIGHTING FOR DECKS AND WATER SURFACES SHALL BE SPACED TO PROVIDE ILLUMINATION TO ALL PORTIONS OF THE DECK AND WATER SURFACE AREAS; BE NOT LESS THAN 0.5 WATTS PER SQ. FT. OF COMBINED WATER/DECK SURFACE AREAS. IF UNDERWATER LIGHTING IS PROVIDED AND IS 0.5 WATT PER SQ. FT WATER SURFACE AREA, THIS AREA NEED NOT BE CALCULATED IN DECK LIGHTING REQUIREMENT.