Notes:
7/16/2018 6:35:56 PM
TENT SITE FOR OCTAGON WITH US YOUTH SOCCER LOCATE ON LOT SOUTH EAST OF PINK FIELD
3 ATTACHED OCTAGONS TOTALING 4200 SQ FT.
PERMIT DOES NOT AUTHORIZE EVENT OR MISC. STRUCTURES.
MAY NOT OBSTRUCT FIRE LANE, HANDICAP PARKING & ACCESSIBILITY, MANDATORY PARKING, STREET TRAFFIC, RIGHT OF WAY, OR VISIBILITY(VAM).
MAY MOUNT ONE BANNER NOT TO EXCEED 48 SQ FT TO TENT WITHOUT ADDITIONAL PERMIT.
ALL AIRBORNE DEVICES (FLAGS, PENNANTS, BALLOONS, ETC.) ARE PROHIBITIED PER ORDINANCE 16-03-25.
SMOKING PROHIBITTED IN ENCLOSED SPACES. REGULATED PER ORDINANCE #06-11-018.
ANY/ALL FOOD PROVISIONS MUST BE APPROVED BY THE HEALTH AND FOOD SAFETY DEPARTMENT UNDER SEPERATE TEMPORARY HEALTH PERMIT.
SUBJECT TO APPROVAL BY FIRE PREVENTION AND POLICE DEPARTMENTS.
PERMIT VALID 07/16/2018 THRU 7/30/2018.
CALL FIRE PREVENTION DEPARTMENT OFFICE FOR TENT INSPECTION AT LEAST ONE WORKING DAY IN ADVANCE AT 972-292-6328.
FIRE PREVENTION DEPARTMENT NOTES:
1. AN INSPECTION FROM THE FIRE PREVENTION DEPARTMENT IS REQUIRED PRIOR TO OCCUPANCY. CALL THE INSPECTION LINE 972-292-6328 TO SCHEDULE.
2. TENT CANNOT OBSTRUCT THE FIRE LANE OR VEHICULAR TRAFFIC FLOW.
3. TENT MUST BE AT LEAST 20 FEET AWAY FROM BUILDINGS, LOT LINES, OTHER TENTS, AND PARKED VEHICLES.
4. NEED TO POST THE OCCUPANT LOAD SIGN FOR THE TENT:
MAXIMUM OCCUPANCY = 280.
5. MINIMUM REQUIRED EXITING FOR 30' X 90' TENT:
5 EXITS AT A MINIMUM OF 72 INCHES WIDE.
6. THE EXITS SHALL BE SPACED AT EQUAL INTERVALS AROUND THE PERIMETER OF THE TENT. PROPER EXITING WIDTH SHALL BE MAINTAINED BETWEEN THE TENT AND OTHER STRUCTURES.
7. AISLE WIDTHS AND EXITS SHALL BE MAINTAINED PER THE 2015 IFC AND IBC.
8. ILLUMINATED EXIT SIGNS WITH TWO SOURCES OF POWER SHALL BE PLACED OVER THE REQUIRED EXITS.
9. NEED TO PROVIDE A 2A10BC "ABC" FIRE EXTINGUISHER.
A. THE FIRE EXTINGUISHER MUST HAVE A CURRENT INSPECTION TAG.
B. THE FIRE EXTINGUISHER SHALL BE PLACED IN THE PATH OF EGRESS AND MOUNTED SO THAT ITS SOP IS NOT MORE THAN 5 FEET ABOVE THE FLOOR.
10. NEED TO PROVIDE AND POST A "NO SMOKING" SIGN ON ALL SIDES OF THE INTERIOR OF THE TENT STRUCTURES.
11. COOKING AREAS MUST BE LOCATED A MINIMUM OF 20 FEET AWAY FROM THE TENT STRUCTURES AND 10 FEET AWAY FROM ANY COMBUSTIBLE MATERIALS OR EXITS.
12. GENERATORS MUST BE A MINIMUM OF 202 FEET AWAY FROM THE TENT STRUCTURES AND SHALL BE ISOLATED FROM CONTACT WITH THE PUBLIC BY FENCING OR OTHER APPROVED METHOD.
13. SMOKING, OPEN FLAMES OR COOKING IS NOT PERMITTED UNDER TENT STRUCTURES.
14. MUST MEET ALL THE MINIMUM REQUIREMENTS OF THE INTERNATIONAL FIRE AND BUILDING CODES.
15. ADDITIONAL REQUIREMENTS MAY BE REQUIRED WHEN A SITE INSPECTION IS CONDUCTED.