Notes:
8613 SQ FT, CNEW / SHOPS AT STARWOOD PHASE TWO
7/31/2006 12:00:00 AM
1. Response letter and plans where submitted 07/31/06.(7/24/2006 13:18 PPB)
Project : Shops at Starwood phase II
Comments and requirements:
1. Submit sheets A401, S200, S400, S401
2. Fire riser room shall be separated by at least 1-hour fire resistive wall construction upto deck.
3. Safety glazing required as per IBC 2406.
4. Crickets required to prevent ponding of water on roof top units.
5. Permanent ladder shall be provided inside the building (fire riser room) to have an access during maintenace of equipments and appliances that is located in the roof.
6. Any tenant space equal or more than 3000 sqft of area shall have vestibule
7. Plumbing and mechanical plans must be signed and sealed by Professional Engineer registered in State of Texas. Submit revised M & P plans.
8. The City of Frisco requires that the building should consider wind load exposure factor as C not B, check and submit if structural design will be affected and submit letter if not.
9. Soil report on the where the building is to build.