Notes:
2740 SQ FT, CIFO / DR RODGERS DERMATOLOGY CLINIC
9/11/2006 12:00:00 AM
Plan review comments;
1. Demising wall shall have at least 1-hour fire resistive construction, therefore wall detail B shall be changed into 1-hour fire resistive construction.
2. Fire/smoke sealed/caulked 1-hour demising wall.
3. Safety glazing required.
4. Any penetrations on 1-hour demising wall shall not reduced its fire resistance rating.
5. Walls shall have a smooth, hard, and non-absorbent surface.
6. Any woods used in a type II - B noncombustible construction shall be fire retardant treated wood.
7. Subject to field inspection.
CONTINGENT UPON COMPLIANCE WITH REVIEW COMMENTS, CODE REQUIREMENT AND PERTINENT LEGISLATIONS.
SUBJECT TO M.E.P. REVIEWS, FIRE MARSHAL AND FIELD INSPECTIONS.
REFER TO APPROVED PLANS FOR NOTES.
ALL SUBCONTRACTORS MUST VALIDATE AND OBTAIN CURRENT REGISTRATION WITH THE CITY PRIOR TO START OF PROJECT.