Notes:
3100 SQ FT, CIFO / STONEBRIAR SMILE DESIGN PA (JILL WADE)
7/25/2007 12:00:00 AM
see notes attached to dwgs. relating to med. gas and storage req'ments.
1. moch fireplace specified.
2. fully sprinkled.
3. IMC 2003 502.8.2, 502.9.1, 502.9.8.1 2003 IFC. proper mechanical ventilation and exhaust for med. gas storage tanks.
4. med. gas storage tanks shall be secured in place by permanent means.
5. cannot use staff lounge area as an exit.
6. all work subject to field approved inspections and testing.
7. interior finishes: flame spread 76--200, smoke developed length 0--450.
8. any wood used shall be fire retardent/treated.
9. 1 hr. demising wall UL-U465.
10. 39" corridor width @ sterilization area minimum.