Notes:
Electrical Ordinance 08-01-10
B10-1841 CLEARWIRE TX. DAL0288
ARTICLE 830 SHALL APPLY TO THIS INSTALLATION
THESE ARE GENERAL NOTES; ITEMS CAN BE VERIFIED IN THE FIELD.
PRIMARY AND SECONDARY PROTECTION IS REQ’D. ON TRANSFORMERS, TAP RULES WILL APPLY.
RELATING TO A ONE HOUR ENCLOSURE------ART. 450-21 A & B
WITH EXCEPT. 1, 2 [CLASS 155 OR HIGHER] WILL APPLY
USE AND IDENTIFICATION OF GROUNDED CONDUCTORS SHALL COMPLY WITH ARTICLE 200.
1. A. MINIMUM #12 COPPER CONDUCTORS PERMITTED EXCEPT FOR CONTROLS.
B. PROVIDE GFCI PROTECTION FOR ALL 15 AND 20 AMP 120 VOLT KITCHEN OUTLETS.
3. ONLY ALUMINIM WIRE PERMITTED IS SERVICE ENTRANCE AND FEEDERS 1/0 AND LARGER STABIL-ALLOY SERIES 6000 & 8000.
4. PULL EQUIPMENT GROUNDS IN ALL RACEWAYS.
7. ALL ELECTRICAL INSTALLATIONS WILL BE SUBJECT TO FIELD INSPECTIONS AND INSPECTOR APPROVALS.
8. ELECTRICAL WILL BE DESIGNED AND INSTALLED PER THE 2005 NATIONAL ELECTRICAL CODE WITH LOCAL AMENDMENTS STATED IN CITY OF FRISCO ORDINANCE ALONG WITH THE FOLLOWING COMMENTS.
10. ALL EXTERIOR LIGHTING SHALL COMPLY WITH COMPREHENSIVE ZONING ORDINANCE ARTICLE IV SECTION 6 LIGHTING & GLARE RQ’MENTS.
11. AN AS-BUILT LEGIBLE PANEL SCHEDULE SHALL BE AFFIXED TO THE INSIDE OF ELECTRICAL PANELS FOR EACH TENANT.
13. GROUNDING AND BONDING SHALL COMPLY WITH ARTICLE 250.
BLDG. STRUCTURAL STEEL, GROUND ROD, COPPER DOMESTIC COLD WATER PIPE (UFER IF AVAILABLE PER 250-81)
17. MAINTAIN PROPER WORKING CLEARANCES IN MECHANICAL/ELECTRICAL ROOM ARTICLE 110-26.
COMM / CLEAR WIRE CELLULAR EQUIPMENT-DAL0288