Notes:
5/16/2019 12:48:12 PM
5/17/2019 8:20:28 AM
Electrical 16-12-101
1- All work performed must meet the 2014 NEC and abide by the city of Frisco Zoning ordinance (13-06-36), and all other city ordinances.
2-Minimum #12 copper conductors permitted except for controls.
4-Lighting COMchecks must match plans.
5-No Aluminum wire permitted or #14. service and feeder conductors permitted 1/0 and larger.
6-Pull equipment grounds in all raceways.
7-Provide exit and emergency lighting as noted and required per 2015 IBC.
8-lighting and controls shall comply with the 2015 IECC where applicable.
9-Available fault current shall be labeled on service equipment 110.24, 2014 NEC.
10-Subject to field review and inspection- call (972) 292-5386 for inspection or schedule online at https://etrakit.friscotexas.gov/