Notes:
INSTALL ONE 13TON HVAC UNIT ON ROOFTOP
11/5/2012 12:00:00 AM
* ALL WORK PERFORMED MUST MEET THE 2006 IRC AND 2006 IMC STANDARDS AND ABIDE BY THE CITY OF FRISCO COMPREHENSIVE ZONING ORDINANCE, AND ALL OTHER CITY ORDINANCES.SUBJECT TO FIELD INSPECTION APPROVAL.
CALL (972) 292-5386 FOR INSPECTION.
(11/6/2012 1:36 PM MBW)
* Mech. installation to comply with the current Frisco amendments of the 2006 IMC & IECC).
*All field installation shall be compliant with the City approved prints. Modifications shall be re-submitted to Plan Review for approval
* Rigid duct required for all HVAC applications. A 6 ft. (R-6) flex duct connector is allowed between the supply duct and the diffuser (see amendments)
* Mech. Engineer & Contractor to be responsible for load calculations and duct sizing (see IMC section 312 & section 603.2). All calculations will be subject to request for review.
* Mech. Engineer to verify ventilation rates and air balance specs.(see IMC 403, IECC 503.2.9, & amendments).
* Subject to field review and inspection.
**INSPECTIONS to be requested are:
-Mech. Final Insp.-Interior and exterior totally trimmed out, gas & elec. meters set, and all equipment and appliances are operable. All equipment must be labeled for location served and cross labeled in elec. panel with same ID number.